+603-8063 0286 sales@sunpoweree.com.my

Inteli AIN8

8 Analog Input Channels and 1 RPM/Impulse Input Module

ComAp’s Inteli AIN8 module allows users to expand the amount of analog inputs for sensors and add Impulse/RPM input that can be attached to a controller. Up to 8 configurable inputs (sensors) can be attached to the controller, and up to ten of the Inteli AIN8 modules can be connected to InteliSys NT, InteliGen NT,InteliMains NT controllers (up to four in case InteliDrive DCUcontroller).

Analog inputs:

Supported sensors:

  • Resistor 3-wire input
    • Common resistor: 0-250Ω, 0-2400Ω, 0-10kΩ
    • Temperature sensor: Pt100, Pt1000, Ni100, Ni1000
  • Current (active or passive sensors)
    • ±20mA , 0-20mA, 4-20mA
  • Voltage
    • ±1V, 0-2,4V, 0-5V, 0-10V
    • Lambda probes
    • Thermocouples are not supported (the measuring loop was designed for lambda probes, what caused non-support of thermocouples)

Impulse/RPM sensor:

  • RPM measuring pulses with frequency  4Hz – 10kHz
  • Impulse
    • Possibility to measure pulses from electrometer, flowmeter (measurement of total consumption, average fuel consumption)

The Inteli AIN8 is determinate for the InteliSys NT, InteliGen NT,InteliMains NT and InteliDrive DCU controllers.